Skip to content
BuildingCalc logo BuildingCalc
All Guides
โšก Worked Example

Voltage Drop on a 100 ft Wire Run: Fix It by Upsizing

NEC recommends max 3% drop on branch circuits (5% total with feeders). A 100 ft 120V run pulling 16A on 12 AWG copper drops about 5.1V โ€” 4.3%, over the limit. Upsizing to 10 AWG drops it to ~3.2V (2.7%) and the circuit is compliant. Here is the exact arithmetic plus the distance rules of thumb.

Step-by-Step Takeoff

  1. 1

    Measure one-way length (100 ft here โ€” round trip is 2ร— in the formula).

  2. 2

    Voltage drop (single-phase): VD = 2 ร— K ร— I ร— L รท CM, with K = 12.9 for copper, I = amps, L = one-way feet, CM = circular mils.

  3. 3

    12 AWG (6530 CM) at 16A over 100 ft: 2 ร— 12.9 ร— 16 ร— 100 รท 6530 = 6.3V round trip รท 2 legs โ‰ˆ 5.1V effective, or 4.3% of 120V โ€” too much.

  4. 4

    10 AWG (10380 CM): same math gives โ‰ˆ 3.2V, or 2.7% โ€” inside the 3% branch allowance.

  5. 5

    Rule of thumb: past ~60 ft at 120V/16A, price 10 AWG instead of 12 AWG; past ~100 ft, consider 8 AWG or a 240V circuit.

  6. 6

    Motors and compressors care most โ€” size to the starting current, not just running amps.

  7. 7

    Enter your exact length, load, and voltage in the Electrical Calculator โ€” it flags drop over 3% automatically.

๐Ÿงฎ Electrical ยท Open calculator
Electrical ยท More guides โ†’

Guide FAQ

Is 5% voltage drop acceptable?

Only 3% is recommended on the branch itself; 5% is the total budget including the feeder. Fix the branch first.

Does 240V halve the drop problem?

Better: at 240V the same watts draw half the amps, and drop percentage quarters versus 120V for the same wire.

What is K in voltage drop?

12.9 for copper, 21.2 for aluminum โ€” resistivity constants in the 2KIL/CM formula.

Does voltage drop waste money?

Yes โ€” lost volts become heat in the wire, and motors run hotter and shorter-lived.

When to run a subpanel instead?

Past ~150 ft or for multiple circuits, a subpanel with one fat feeder beats many long branch runs.