Voltage Drop on a 100 ft Run: How to Fix It
NEC recommends max 3% drop on branch circuits (5% total with feeders). A 100 ft 120V run pulling 16A on 12 AWG copper drops about 6.3V — 5.3%, well over the 3% target. Upsizing to 10 AWG cuts it to ~4.0V (3.3%), still just above target; 8 AWG brings it to 2.5V (2.1%) and the circuit is compliant. Here is the exact arithmetic plus the distance rules of thumb.
💡 At a Glance
A 100 ft 120V run at 16A on 12 AWG drops 6.3V (5.3%) — 10 AWG cuts it to 3.3%, and 8 AWG passes at 2.1%.
ƒx Key Formula
VD = 2 × K × I × L ÷ CM; K = 12.9 copper, L = one-way feet, CM = circular mils
Step-by-Step Takeoff
-
1
Measure one-way length (100 ft here — round trip is 2× in the formula).
-
2
Voltage drop (single-phase): VD = 2 × K × I × L ÷ CM, with K = 12.9 for copper, I = amps, L = one-way feet, CM = circular mils.
-
3
12 AWG (6530 CM) at 16A over 100 ft: 2 × 12.9 × 16 × 100 ÷ 6530 = 6.3V total drop, or 5.3% of 120V — too much.
-
4
10 AWG (10380 CM): same math gives ≈ 4.0V, or 3.3% — still just over the 3% target; 8 AWG (16510 CM) gives 2.5V, or 2.1%, which passes.
-
5
Rule of thumb: past ~60 ft at 120V/16A, price 10 AWG instead of 12 AWG; past ~100 ft, consider 8 AWG or a 240V circuit.
-
6
Motors and compressors care most — size to the starting current, not just running amps.
-
7
Enter your exact length, load, and voltage in the Electrical Calculator — it flags drop over 3% automatically.
⚠️ Common Mistakes
-
1
Measuring the loop instead of one-way length — the formula already doubles for the return leg.
-
2
Accepting 5% on the branch — 5% is the feeder-plus-branch budget; the branch itself gets 3%.
-
3
Ignoring motor loads — compressors and pumps care about starting current, not running amps.
Guide FAQ
Is 5% voltage drop acceptable?
Only 3% is recommended on the branch itself; 5% is the total budget including the feeder. Fix the branch first.
Does 240V halve the drop problem?
Better: at 240V the same watts draw half the amps, and drop percentage quarters versus 120V for the same wire.
What is K in voltage drop?
12.9 for copper, 21.2 for aluminum — resistivity constants in the 2KIL/CM formula.
Does voltage drop waste money?
Yes — lost volts become heat in the wire, and motors run hotter and shorter-lived.
When to run a subpanel instead?
Past ~150 ft or for multiple circuits, a subpanel with one fat feeder beats many long branch runs.
Related Guides
What Wire Size for a 20A Branch Circuit?
12 AWG copper on a 20A breaker: ampacity, the 80% continuous-load rule, and when to upsize.
Is My 200A Panel Overloaded? Do the Math
Existing 80A load plus new circuits against a 200A service, demand factors, and upgrade triggers.
How Many Wires Fit in 3/4" PVC Conduit?
The 40% fill rule worked: THHN areas by gauge, derating limits, and conduit upsizing calls.