3/4英寸PVC管能穿几根线?
规范将3根以上导线的穿管填充率上限为40%(发热和穿线损伤)。3/4英寸PVC管(Sch40)在40%下可用约0.213平方英寸。四根12AWG THHN(每根0.0133,合计约0.053)轻松穿入;9根是实际个上限,再多降额就逼着用更粗的线。以下是计数法加降额陷阱。
💡 At a Glance
3/4" PVC at 40% fill holds about 16 × 12 AWG THHN — but derating above 9 conductors usually governs first.
ƒx Key Formula
Fill = Σ conductor areas ÷ (0.40 × conduit area); derate at 4–6 (80%), 7–9 (70%) conductors
Step-by-Step Takeoff
-
1
查可用面积:3/4英寸PVC按40%约0.213平方英寸(计算器内置PVC/EMT表)。
-
2
查带绝缘导线面积:12AWG THHN约0.0133平方英寸,10AWG约0.0211。
-
3
相除:0.213 ÷ 0.0133 ≈ 按填充可穿16根 - 但9根以上降额通常先起作用。
-
4
用降额:4-6根→80%载流;7-9根→70%;降额后低于断路器就要加大。
-
5
按规范把地线和零线计入载流;每根都占填充。
-
6
长线路或弯多的留穿线绳加25%余量。
-
7
在电气计算器穿管面板定管径、计数,再按英尺计价。
⚠️ Common Mistakes
-
1
Using estimates instead of Chapter 9 Table 5 — each THHN size has a published area; sum those.
-
2
Forgetting ground wires count toward fill — they take space even when they skip derating.
-
3
Assuming more wires always fit — derating drops ampacity, often forcing a bigger wire or conduit.
Guide FAQ
地线计入填充吗?
计入,设备地线占填充(但降额时不一定计)。
一根管能混线规吗?
能 - 按第9章表5累加每根面积,保持在该管径40%以内。
1/2英寸EMT穿几根12AWG?
按40%为9根 - 但7-9根时降额常逼用10AWG。
短管箍要降额吗?
24英寸以下管箍按60%填充且免降额 - 实用的例外。
室内用PVC还是EMT?
EMT更细、可自接地、好穿线;埋地和腐蚀环境PVC胜。